| Install | Same precharged 25-ft quick-connect lineset as the 12k — hang, connect, torque, open valves, no vacuum pump. The difference is power: it needs a dedicated 208/230V circuit (30A breaker territory), so budget for an electrician or a subpanel run if you don't have 240V nearby. | Precharged 25-ft R-454B Quick Connect lineset (1/4" x 1/2"), no vacuum pump, same as the rest of the DIY line. Power is a dedicated 208/230V circuit; MRCOOL's spec sheet lists an 18A minimum circuit ampacity and 20A maximum fuse, so a 20A double-pole breaker covers it. The condenser is about 93 lb, a two-person carry if stairs are involved. Seal the wall penetration with putty or silicone, not expanding foam: the air handler's R-454B leak sensor can read curing foam as a leak. |
|---|